Fire Safety of Onboard Battery Rooms (BESS)
BESS response follows the approved emergency plan and installed design: alarm, segregation only as designed, ventilation control and approved fixed suppression/cooling from a safe position; no entry until explosion/toxic risk is assessed and authorised.
Operational Explanation
BESS response follows the approved emergency plan and installed design: alarm, segregation only as designed, ventilation control and approved fixed suppression/cooling from a safe position; no entry until explosion/toxic risk is assessed and authorised.
Regulatory Reference
Approved flag/class design and SMS; EMSA BESS Guidance is non-mandatory; SOLAS II-2/17 only where it is the actual alternative-design route.
For lithium-ion batteries, thermal runaway can release toxic and flammable gases and spread to other cells. Absence of flames does not establish that the event has stopped: maintain the prescribed monitoring and measures against re-ignition, gas accumulation and damage to adjacent compartments. EMSA BESS Guidance, fire and explosion hazards.
Ventilation and extinguishment must follow a coordinated strategy: gas extraction and inerting agents may require different arrangements. Do not transfer a generic ventilation shutdown sequence to the BESS room; use the approved plan’s controls and sequence and keep hazardous areas near exhaust outlets clear. EMSA BESS Guidance, ventilation and extinguishment.
Scope of Application
Training, familiarisation and drills to the extent required by approved design, risk assessment, flag/class and SMS; not automatically every drill for every hybrid ship.
Procedure / How to Complete It
- From a safe position raise alarm and identify the event.
- Stop/segregate only as designed.
- Control ventilation and activate the approved fixed strategy.
- Do not generically apply water or electrical isolation.
- Prohibit entry until explosion/toxic-atmosphere risk is assessed and entry authorised.
- Integrate hazards into training/drills under the approved regime.
Practical Example
The plan may use water-based, inerting or combined means: the team uses the installed system and does not enter merely because visible flame has ceased.
What Typically Goes Wrong
Imposing massive and prolonged cooling, improvising isolation/water, entering before risk clearance, or treating EMSA/drills as universally mandatory.
Common Mistakes Mistake Library
| Mistake | Consequence | How to Avoid It |
|---|---|---|
| Imposing massive and prolonged cooling, improvising isolation/water, entering before risk clearance, or treating EMSA/drills as universally mandatory. | Non-compliant decision or treatment | Follow the approved arrangement and applicable sources |
What the PSCO Checks
Operational Tips
- Separate current requirement, class/maker, SMS and voluntary guidance.
- Do not improvise tests, thresholds or intervals.
- Record deviations and corrective action.
Preparation checklist
- Approved response plan
- Remote safe controls
- Ventilation/suppression design
- Explosion/toxic entry gate
- Approved training scope
- EMSA non-mandatory
FAQ